GX-2009 Specifications
|
Sampling Method
|
Diffusion sampling standard / hand aspirator or motorized pump optional
|
Display
|
Digital LCD displays all four gases simultaneously, with auto backlight
|
Types of Alarms
|
Gas Alarm: 2 Increasing alarms, STEL, TWA, overscale alarm. O2 decreasing/increasing. Trouble alarm: Sensor disconnection, low battery, circuit error, calibration range error
|
Display of Alarm
|
Gas Alarm: Flashing LEDs, intermittent buzzer (95 db @ 30 cm), flashing gas value, vibration Trouble alarm: Flashing LEDs, intermittent buzzer (95 db @ 30 cm), display of error message
|
Operating Temp. & Humidity
|
-4°F to 122°F (-20°C ~ +50°C), 0 to 95% RH, non-condensing (splash resistant)
|
Response Time
|
Within 30 seconds (T90)
|
Continuous Operation
|
20 hours after a 3 hour full charge (14 hours after 90 min charge)
|
Power Source
|
Direct charging NiMH batteries, set of 2
|
Safety Design / Approvals
|
IECEx zone 0 Ex ia IIC T4; ATEX II 1G Ex ia IIC T4; (optional MSHA version also available) c CSA us classified, as intrinsically safe. Class I, Division 1, Groups A, B, C, D
|
Dimension & Weight
|
2.7” H x 3” W x 1” D (Approx. 70 H x 75 W x 25 D mm), 4.6 ounces (approx. 130 g)
|
Case Material
|
High impact over molded rubber. Dust and water resistant with IP-67 approval.
|
Controls
|
Two buttons: POWER / MODE, AIR
|
Datalogging
|
Standard with all instruments. Stores 8 alarm trend sessions where readings are recorded 30 minutes before and after an alarm event. 3,600 data point capacity with a log time range of 10 to 300 hours (based on programmable interval times); and stores up to 100 calibration records.
|
Sensor Specs
|
Combustible Gases (LEL)
- Range: 0 ~ 100% LEL (1% LEL increments)
- Accuracy: ± 5% of reading or ± 2% LEL (whichever is greater)
- Preset Alarms: 1st alarm 10% LEL, 2nd alarm 50% LEL, Over alarm 100% LEL
Oxygen (O2)
- Range: 0 ~ 40.0% Vol. (0.1% Vol. increments)
- Accuracy: ± 0.5% O2
- Preset Alarms: Low alarm 19.5%, High alarm 23.5%, Over alarm 40.0%
Carbon Monoxide (CO)
- Range: 0 ~ 500 ppm (1 ppm increments)
- Accuracy: ± 5% of reading or ± 5 ppm CO (whichever is greater)
- Preset Alarms: 1st alarm 25 ppm, 2nd alarm 50 ppm, TWA alarm 25 ppm, STEL alarm 200 ppm, Over alarm 500 ppm
Hydrogen Sulfide (H2S)
- Range: 0 ~ 100.0 ppm (0.5 ppm increments)
- Accuracy: ± 5% of reading or ± 2 ppm H2S (whichever is greater)
- Preset Alarms: 1st alarm 5 ppm, 2nd alarm 30 ppm, TWA alarm 1 ppm, STEL alarm 5 ppm, Over alarm 100 ppm
|
Warranty
|
Two years material and workmanship
|